Vaillant F75 Fault Code: What It Means and What to Do
Boilers
2026-11-26

Vaillant F75 Fault Code: What It Means and What to Do

Vaillant F75 with the gauge at 1.5 bar? Topping up won't touch it. When it's low pressure you can sort yourself, and when it's the sensor or pump.

SM
Macara Heating Team5 minute read

Quick read

The display shows the same F.75 whether the gauge reads 0.6 or 1.5 bar, and the fix is completely different for each.
A wet streak on the outside wall under the boiler's copper pipe is worth a photo for whoever comes out.
Still under Vaillant's warranty? Have the serial number off the data label to hand when you ring them.

F.75 on a Vaillant means the boiler started its pump and didn't see the pressure rise it was waiting for. Every time the pump kicks in there should be a small pressure jump in the heating water, and a water pressure sensor inside the case watches for it as proof the water's actually going round. No jump and the boiler locks out with F75 on the display, same code on an ecoTEC plus or an ecoTEC pro combi. Some of the older manuals word it as a pump or water shortage fault.

Go and read the boiler pressure before you do anything else, heating off and the radiators cold. Depending how old the boiler is that's a wee dial on the front or a number on the display. Under 1 bar is the good news, believe it or not, because that's usually one you can sort with the filling loop. If it's sat at 1.5 like it should be then the water's fine and something behind the front case isn't, so skip down a couple of sections.

Boiler pressure under 1 bar: topping up at the filling loop

Vaillant give 1 to 1.5 bar as normal with the system cold. The ecoTEC plus manual lets it go up to 2 bar cold, a bit higher on a house with a few storeys, so your installer might have set it a touch higher than you'd expect.

On some ecoTEC combis it's built in underneath, on others it's a silver braided hose with a tap at each end that's meant to come off after use and very often lives in the kitchen drawer with the batteries and the takeaway menus. Get the manual for your model out and only do it if you're comfortable. Open it slowly and watch the gauge climb, stop at about 1.5 and close both valves right off, a valve left cracked keeps feeding water in and you'll be looking at 3 bar by teatime.

Gauge well over 2 bar cold to start with is the other problem altogether, boiler pressure too high covers it.

Topped up and F.75 gone? Keep an eye on the gauge for a few days though, because the water you put back in went somewhere first. If it's drifting down again read why a boiler keeps losing pressure.

Leaks and air in the system

Low pressure means water's getting out, so go looking. Radiator valves first, where the valve meets the pipe, and look for green or white crust as much as drips because a slow weep dries off before it ever reaches the carpet. Then under the boiler and round the pipework beneath it.

And outside. There's a copper pipe from the boiler's pressure relief valve out through the wall, usually short and pointing down at the ground, and if there's a drip on the end of it or a damp line down the harl the valve has been letting water go. Found water anywhere, boiler leaking water has what to do next.

Air in the system shows up as gurgling in the pipes and radiators hot at the bottom and cold across the top. It gets into the pump as well and a pump with air in it can't push the pressure up for the sensor to see. Why one radiator is cold shows you how to bleed one. Bleeding lets water out along with the air, so check the gauge again when you're done, it's easy enough to bleed three radiators and talk yourself straight back into F.75.

F.75 with the pressure sitting fine at 1.5 bar

This is most of the F.75 calls we get. Gauge reads 1.5, nothing's leaking, nobody's touched anything, and the boiler locks out the minute the heating comes on. There's water in the system, plenty of it, and the boiler still can't tell it's moving.

On a Vaillant ecoTEC the water pressure sensor is first in line. It's a small part inside the case and when it starts to go it reads wrong or slow and misses a pressure jump that's really happening, older boilers more so. Swapping it doesn't always cure it mind. On a system that's run twenty-odd years with no filter on it sludge settles in the narrow port the sensor reads through and blocks it, so a brand new sensor reads the same nothing the old one did. Bleed a radiator and get black water and you've a fair idea what's going on in there. (Old cast iron column radiators in a Marchmont or Leith tenement are the worst for it, they hold a lot of water and a lot of muck.)

Then the circulation pump. Seized, sticking after a summer of doing nothing or just tired, a weak pump won't make enough of a jump for the sensor.

The expansion vessel is a sideways one. Lose its air charge and the pressure swings, climbs when the system's hot, dumps out that copper pipe, then sits low when it cools, so it tends to turn up as a low pressure F.75 that keeps coming back. Wiring and the PCB come last, a broken connection to the sensor or pump will do it.

All of that's behind the casing and the casing stays on. Every one of these checks gets done by a qualified Gas Safe engineer with the power isolated. DON'T take the cover off for a look because you've watched somebody do it on YouTube.

Resetting F75 on an ecoTEC

Reset button on the front, the fault clearance button in some of the manuals, pressed ONCE after the pressure's right. If F.75 is back as soon as the pump starts, stop pressing.

Vaillant warranty first, then us

Dig the paperwork out before anything else. A boiler still inside its Vaillant manufacturer warranty should go to Vaillant first, and it's worth knowing what's covered before you pay anybody independent to touch it.

Out of warranty, or you'd just rather have someone local, we're Gas Safe registered and do boiler repair across Edinburgh, Dalkeith and the Lothians. Phone 0131 644 0045 and tell us the model, the pressure you read cold and whether you've topped up or bled anything, or use the repair request form. How we go about a callout is on the boiler repairs page. If the display says F.28 and not F.75 that's ignition and a different job, the Vaillant F28 guide has it.

Common Questions

Vaillant F75 questions

The ones we get on the phone about F.75 on an ecoTEC.

The pump started and the pressure sensor never saw the wee pressure rise it checks for.