Quick read
Lit, then lost it. That's the Ideal telling you the burner fired and the board stopped seeing a flame a few seconds later, so it shut the gas valve rather than keep feeding unburnt gas into the chamber. Some of the newer Ideal screens spell the fault out in words instead of a two-character code so if yours doesn't say F2 as such, the booklet is your friend.
If there's a smell of gas in the house though stop reading this. Open the windows, turn the meter off at the handle if you can get at it safely, don't flick a light switch or strike anything and phone the National Gas Emergency Service on 0800 111 999.
Go and light the hob
Before you book anybody. If the hob's dead too then the boiler is very probably fine and it's the supply, and on prepay meters that usually means the emergency credit ran out and it just stopped, no beep, no warning. In Edinburgh tenements the meter tends to live in a hall cupboard with the hoover and four winters of jackets and it's amazing how often the emergency control handle gets knocked half shut by somebody rummaging for a brush (those cupboards end up with meters buried behind paint tins and bikes). Credit on it, handle open, and still nothing gas-fired works anywhere in the flat? Ring your gas supplier.
Hob lights fine. Right, then crouch down and look under the boiler for the yellow-handled isolation valve on the gas pipe. If the handle sits across the pipe somebody shut it, and if you don't know who or why leave it alone, it could have been isolated for a leak or after a previous job and that wants checking before anyone opens it back up.
With the cover off
We'd start at the flame probe. Thin rod that sits in the flame so the board can tell the gas is burning and not just pouring out. Carbon on the tip will do it, so will the lead going brittle where it runs past the hot side of the boiler, and you get a burner that lights for three or four seconds and drops out. Folk hear that on a Logic and decide the board's gone. Usually it hasn't.
If the probe checks out the manometer goes on the test point with the boiler firing, because pressure at the meter can look perfect with nothing running and then sag the second a combi pulls hard for the shower, old 15mm that was put in for a cooker and a gas fire is usually why. Could be the gas valve sticking as well. Then there's the flue seals and the condensate trap inside the case and all that wants proving before anybody prices up a PCB on a Logic Max or a Vogue, boards do go but not half as often as people think.
None of that is homeowner stuff. Keep the casing on, it's gas and combustion kit behind it and it needs a Gas Safe engineer with proper test gear.
The reset button
Press it ONCE, older Logics hide it on the mode dial behind the little drop-down flap. If F2 comes back you're only putting the boiler through more failed light-ups so stop there.
When it isn't really F2
Ideal put F2 and L2 on the same help page which doesn't help anybody, L2 means it never lit in the first place and that's covered in our Ideal L2 fault guide. Needle on the floor of the pressure gauge is F1 territory on an Ideal, most sealed systems want somewhere about 1 to 1.5 bar cold, so look at the Ideal F1 guide or why a boiler keeps losing pressure if it keeps dropping.
And a frozen condensate pipe is more of an L2 thing, being honest. But if it was minus four out by the Pentlands overnight and the boiler was gurgling before it died go and look at the white plastic pipe coming out the wall. Only if you can reach it with both feet on the ground. Warm water from a jug or a hot water bottle, NEVER boiling, no ladders, and the frozen condensate pipe guide has the full method.
Still under warranty?
Dig the paperwork out before you pay anyone. Ideal want warranty boilers reported to them first and there's no sense paying for a repair they'd have done anyway.
Out of warranty and cold in Edinburgh, Dalkeith or anywhere round the Lothians, phone us on 0131 644 0045 with the model and what you've already ruled out, or put it through the boiler repair form. How we handle callouts is on the boiler repairs page.
Ideal F2 fault questions
The things people ask us when the Ideal starts flashing F2.
Flame loss, on an Ideal anyway. Other makes use F2 for different faults altogether.